1076188 - TRIO-PS-2G/3AC/72DC/14
Primary-switched TRIO power supply for DIN rail mounting, input: 3-phase, output: 72 V DC/14 A, dynamic boost, tool-free fast connection technology for rigid and flexible conductors with ferrule
AC operation | |
Network type | Star network |
Nominal input voltage range | 3x 400 V AC ... 500 V AC |
Input voltage range | 3x 400 V AC ... 500 V AC -20 % ... +15 % |
Typical national grid voltage | 3x 400 V AC |
3x 480 V AC | |
Voltage type of supply voltage | AC |
Inrush current | ≤ 30 A (typical) |
Inrush current integral (I2t) | < 1.1 A2s |
Inrush current limitation | 35 A (after 1 ms) |
AC frequency range | 50 Hz ... 60 Hz |
Frequency range (fN) | 50 Hz ... 60 Hz ±5 Hz |
Mains buffering time | > 10 ms (400 V AC) |
> 20 ms (480 V AC) | |
Current consumption | 3x 1.9 A (400 V AC) |
3x 1.7 A (500 V AC) | |
Nominal power consumption | 1335.1 VA |
Protective circuit | Transient surge protection; Varistor |
Power factor (cos phi) | 0.77 |
Typical response time | < 1 s |
Input fuse | 6.3 A (internal (device protection)) |
Recommended breaker for input protection | 10 A ... 16 A (Characteristics B, C, D, K) |
Discharge current to PE | < 3.5 mA |
< 2.5 mA (550 V AC, 60 Hz) |